| Macon Specification | |||||||||
| Valve - Macon Straight, Vertical
Angle, Horizontal Angle or Copper x Copper Sweat as Required: Forged brass, nickel plated, female inlet, male union outlet or copper x copper brass body EPDM seat suitable for 15 psi steam, 250°F hot water, maximum static pressure 145psi Replaceable insert assembly with raised knurled serrations and stainless steel spindle and stainless steel spring
|
|||||||||
| Direct Mount Thermostat - Macon Model
ENT B26000: Direct acting, built in sensor, wax filled, hysteresis .9°F, max movement per 1°F = .007 Range 46°-80°F with limit and locking features Must have positive shut off, maximum differential pressure 20psi Heat diffusing rings and knurled serration that lock the thermostatic dial to the valve body Tamper proof, Non-Removable high impact plastic protection rings 24 month warranty, and must conform to ASHRAE Standard 102p-1983 |
|||||||||
![]() ENT B26000 |
|||||||||
| Remote Sensor Thermostat - Macon
Model ENTZ-B36000: Valve mounted setting knob with remote temperature sensor Capillary to be stainless steel, 78" long minimum Provide high impact plastic sensor guard Temperature range 46-80°F, with limit and locking features Must have positive shut off, maximum differential pressure 20psi Heat diffusing rings and knurled serration that lock the thermostatic dial to the valve body 24 month warranty, and must conform to ASHRAE Standard 102p-1983 |
|||||||||
![]() ENT B36000 |
|||||||||
| Remote Dial Thermostat Model Macon
ENTL-B46000: Remote mounted dial with sensor behind dial, minimum 78" stainless steel capillary High impact plastic dial operator, range 46°-80°F with limit and locking features Must have positive shut off, maximum pressure differential 20psi 24 month warranty, and must conform to ASHRAE Standard 102p-1983 |
|||||||||
ENTL B46000 |
|||||||||
| Combination Remote Dial / Remote
Sensor Thermostat - Macon Model ENTLZ-B56000: Combination remote setting dial/remote sensor, minimum 78" stainless steel capillary to setting dial and 78" stainless steel capillary to temperature sensor Requires the capability to remove temperature sensor from dial with minimum 78" S.S. capillary Provide high impact plastic sensor guard Temperature range 46-80°F, with limit and locking features Must have positive shut off, maximum differential pressure 20psi 24 month warranty, and must conform to ASHRAE Standard 102p-1983 |
|||||||||
ENTLZ B56000 |
|||||||||
| |
|||||||||
|
|||||||||
|
Home - Valves &
Controls - Conversion Kits -
Specs - Valves OPSK - Thermostats - Cross Ref - Flair® |
|||||||||